PRESSURE REDUCING LANDING VALVE
- Product Code: FHA-0065
- Availability: In Stock
DESCRIPTION
pressure-reducing oblique landing valves are suitable for installation on wet risers in buildings for fire fighting purposes, permanently charged with water from a pressurized supply.
These landing valves are a pressure-reducing type designed to provide a range of outlet pressure (4 bar -12 bar). The Landing valves are classified under high pressure and are suitable for use at a nominal inlet pressure of up to 20 bar.
SPECIFICATION
Model No. | NWR 120 |
---|---|
Valve Type | Oblique, Pressure Reducing, Flanged Inlet |
Pressure Rating | High Pressure Valve |
Nominal Size | DN50 |
Working Pressure | 20 Bar Maximum |
Test Pressure | Valve Seat Test at 22 Bar • Body Test at 30 Bar |
Flange Drilling | BS4504 Part: 2 :1974Table: 16/2 |
Min. Water Flow Rate | 8.5 L/S @ 4 Bar Outlet Pressure |
Min. Valve Pressure Regulating | 4-12 Bar |
FEATURES
- BSI Kitemark approved
- Body material made of copper alloy to EN 1982
- Hand wheel material made of grey cast iron to BS EN 1561
- Blank cap material made of copper alloy to EN 1982
- Possible to replace the gland seal when under pressure with the valve fully closed
- Disc-facing rubber is of replaceable type
- Valves are provided with a strap and padlock so that the hand wheel can be secured to counter unauthorized use
- The hand wheel is BLACK painted and the body to RED